INPUT: 90...265 V AC
OUTPUT: 24...28 V DC
Current: 5 A
OUTPUT: 24...28 V DC
Current: 5 A
General data
Standards | IEC 61010-2-201, EN 61204-3, EN 55022 B, EN 61000-3-2 |
---|---|
Mounting method | DIN-rail mountable TH35 (EN 60715) |
Efficiency | 83% (115 V AC); 87% (230 V AC) |
Relative humidity | 5...95%, no condensation |
Dimensions H×W×D | 115×54×151 mm |
Temperature range | 0...+60 °C (storage temperature -25...+85 °C) |
Output
Output voltage | 24 V DC (SELV), ±1%; 24...28 V adjustable |
---|---|
Output current | 5 A (+60 °C); 6 A (+40 °C, 110...265 V AC) |
Mains failure bridging time | min. 18 ms (230 V AC) |
Ripple | max. 20 mV eff/rms |
Spikes | max. 80 mV ss/pp |
Unit protection | short-circuit and overload protected |
LED display | LED (green) for output voltage |
Selectable switch-off mode | front sided plug link (automatic re-start or definite shut-off) |
Parallel usage/serial usage | max. 5 units/max. 2 units |
Input
Input voltage | 90...265 V AC |
---|---|
Input current | 1.4 A (100 V AC); 0.6 A (230 V AC) |
Inrush current after 1 ms | max. 25 A |
Primary fusing external | max. 10 A |
Frequency | 50...60 Hz |
Commercial data
country of origin | CZ |
---|---|
customs tariff number | 85044090 |
EAN | 4048879080675 |
eClass | 27049002 |
Packaging unit | 1 |